← Home · In-Situ Testing

Field Permeability Testing (Lefranc/Lugeon) in Wollongong

Together, we solve the challenges of tomorrow.

LEARN MORE →

In Wollongong, you can have competent Hawkesbury sandstone on one block and colluvial silts on the next. We see this every week. A standard borehole log gives you strength. It doesn't tell you how water moves through the fractures. That's why we run field permeability tests using the Lefranc method in soils and the Lugeon method in rock. The data goes directly into the dewatering plan. We do the test. We interpret the result. No extrapolating from grain size curves. AS 1726 gives the framework. Our local experience gives the context. For projects near the escarpment, where the water table responds to rainfall within hours, you need numbers you can trust. A CPT test can map the stratigraphy, but only a Lefranc or Lugeon test measures the mass permeability of the formation.

A permeability value from a disturbed lab sample is a guess. A Lefranc or Lugeon test gives you the mass permeability of the formation as it sits.

How we work

A recent excavation on Crown Street hit a fractured sandstone lens at 4 metres. The contractor expected a dry cut. Water inflow started within 20 minutes. The design had assumed a Lugeon value from a desktop study. We mobilised within 48 hours, ran a series of Lugeon tests in the fractured zone, and delivered revised values. The contractor adjusted the dewatering system and the cut was stable within three shifts. That's the difference between a lab number and a field number. For the soil horizons above the rock, we run the Lefranc test at multiple depths. The setup is simple: a sealed test interval, constant head or falling head, and a stable reading. We don't rush the saturation phase. In Wollongong's colluvial clays, you need patience to get a representative value. The data pairs well with a grain size analysis to understand the transport mechanism in the fine fraction.
Field Permeability Testing (Lefranc/Lugeon) in Wollongong
Technical reference image — Wollongong

Site-specific factors

The risk profile changes completely between the Port Kembla flatlands and the Figtree slopes. In Port Kembla, you're dealing with hydraulic fill and perched water tables. A Lefranc test that shows 1x10^-5 m/s means you'll be pumping a lot of water from a modest excavation. In Figtree, the same numerical value in a residual soil profile over shallow rock might indicate a preferential flow path along the bedrock interface. The number is the same. The engineering consequence is different. Ignoring this distinction leads to under-designed sump systems and flooded footings. We've seen it. The Lugeon value in the sandstone also varies by orders of magnitude depending on fracture aperture and infill. A value below 3 Lugeon means you won't grout it. A value above 10 means you will. Getting that boundary right saves tens of thousands in grout.

Need a geotechnical assessment?

Reply within 24h.

Email: [email protected]

Reference parameters

ParameterTypical value
Test method (soil)Lefranc – constant head / falling head
Test method (rock)Lugeon – 5 pressure stages per AS 1726
Test interval in rockTypically 3 to 5 metres, isolated with pneumatic packer
Measurement range (soil)10^-5 to 10^-8 m/s depending on soil type
Lugeon value interpretationLess than 3: low permeability; greater than 10: grouting required
Reporting standardAS 1726: Geotechnical site investigations
Data outputFlow vs. pressure plots, Lugeon values per stage, Lefranc k value

Associated technical services

01

Lefranc testing in overburden

Constant and falling head tests in soil boreholes. We isolate the test zone with a sand pack and bentonite seal to prevent short-circuiting along the casing.

02

Lugeon testing in rock

Five-stage pressure testing in NMLC or HWLX boreholes using pneumatic packers. We record flow at each pressure step and plot the flow-pressure curve to identify fracture flow regime.

03

Dewatering assessment packages

Combined Lefranc and Lugeon data integrated into a conceptual site model. We provide the k values you need for analytical or numerical dewatering models.

04

Grouting verification

Pre- and post-grouting Lugeon tests to verify the effectiveness of curtain or consolidation grouting programs in fractured rock masses.

Applicable standards

AS 1726: Geotechnical site investigations, AS 4678: Earth-retaining structures, AS/NZS 1170 series: Structural design actions

Quick answers

When should I specify a Lugeon test instead of a Lefranc test?

Specify a Lugeon test in rock or very stiff cemented materials where you drill with rotary methods and can isolate a test interval with a packer. The rule of thumb: if you need a core barrel to advance the hole, you need a Lugeon test. Use the Lefranc test in soils where the borehole stays open or is supported by a slotted casing and a sand filter. In Wollongong, many sites have a soil profile overlying sandstone, so you'll need both. Lefranc in the upper 3 to 6 metres, Lugeon in the rock below.

How long does a field permeability test take on site?

A single Lefranc test in moderate-permeability soil can be completed in 1 to 2 hours once the test interval is prepared. A Lugeon test in rock typically takes 45 to 90 minutes per 5-metre interval, running all five pressure stages. We always allow time for the test zone to saturate and for flow to stabilise before recording data. In low-permeability materials, the test duration increases because the flow rate takes longer to reach equilibrium.

What does a Lefranc or Lugeon test cost in the Wollongong area?

For a typical investigation in the Wollongong region, a field permeability test ranges from AU$900 to AU$1,770 per test interval. The final cost depends on the depth of the test, the number of intervals required, and the access conditions on site. Mobilisation is additional. We provide a fixed-price quote once we review the borehole logs and the testing depth.

What Lugeon value indicates that rock grouting is needed?

We use the Houlsby interpretation method. A Lugeon value below 3 typically indicates tight rock that does not require grouting. Values between 3 and 10 suggest moderate permeability where grouting depends on the project's water-tightness requirements. A Lugeon value above 10 indicates open fractures and a rock mass that will take grout. For dam foundations and cutoff walls, the acceptance threshold is often set at 3 to 5 Lugeon after grouting.

Location and service area

We serve projects in Wollongong and surrounding areas.

View larger map